Permit Information
Permit NumberFIR06-00112
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - SLRMC
Customer Number 
ePlanReview 
Description
To provide required sprinkler monitoring for the four new sprinkler system floor control valve zone/alarms (Two (2) ea, flow and control valve monitoring, 10th floor in Stair #1; one (1) ea, flow and control valve monitoring, East Annex elevator machine room; one (1) ea, flow and control valve monitoring, north mechanical penthouse).

Additional heat detectors are being added to the elevator machine rooms (12th floor, five (5) ea; 11th floor, one (1) ea).

Manual pull stations are being installed in the 12th floor elevator machine room and the 11th floor elevator lobby to the roof.

Total notification is being added to the north mechanical penthouse, Helipad area, 11th and 12th floor elevator lobbies and East Annex elevator machine room. A new NAC panel will be added for 11th and 12th floor.

A copy of the sprinkler plans indicate floor controls being added to the 3rd and 4th floors. The PDS Fire Inspector shall field verify. A plan modification (resubmittal) will be required if these sprinkler monitoring points are new and not monitored by the fire alarm system.

The associated sprinkler permit (FIR05-00846) is to install 4 new floor control valve zone/alarm. The four locations addressed are Heliport, Public Elevator Machine Room, East Annex Elevator Penthouse and the North Penthouse. St Lukes Regional Medical Center *
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20065/1/20065/1/2006APASS
DetailsForrest France
Fire alarm corrections have been verified, permit work passed final inspection.
INSP-Final Inspection4/27/20064/28/20064/28/2006AFAIL
DetailsForrest France
Tested notification and detection devices at the 10th and 11th floor machine rooms, helipad, elevator lobbies, mech. penthouse, tested manual pulls, smoke at nac panel, tested sprinkler tampers and flows at the 10th floor manifold. The notification devices at the north mech. penthouse 3rd floor failed to function properly, need to test sprinkler tampers and flows at the 4th floor and tamper at the 3rd floor at next inspection.
INSP-Final Inspection4/24/20064/26/20064/27/2006PFAIL
DetailsForrest France
Waterflow alarms are addressed incorrectly, system has not been pre-tested prior to inspection, to be rescheduled.