Permit Information
Permit NumberFIR06-00210
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 4650 N GINZEL RD
Project NameSPR BUSTER BUILT RESIDENCE
Customer Number 
ePlanReview 
Description
BUSTER BUILT * To install a (modified) life safety NFPA 13D system in a 2,362-ft/2, multi-level, single family dwelling (932-ft/2 lower level, 1182-ft/2 main level, 248-ft/2 upper level, 576-ft/2 attached garage). Fire sprinkler supply and backflow preventer shall be installed by others, but will require complete coordination and verification of meeting minimum installation fire code by the contractor through this permit. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-00210.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/1/20068/2/20068/2/2006APASS
DetailsForrest France
Final inspection passed permit finaled.
INSP-Final Inspection7/31/20068/1/20068/1/2006AFAIL
DetailsForrest France
Inspectors test and main drain line not completed to allow final testing, need to attatch hyd. calc. sticker, provide locking means for the main control valves, one painted head under the stairs was replaced while on site.
INSP-Supply line flush7/31/20068/1/20068/1/2006APART
DetailsForrest France
UG supply line flush performed satisfactory.
INSP-Sprinkler Rough-in4/28/20065/1/20065/1/2006APASS
DetailsTroy Cobbley
Per David, the sprinkler fitter there is to be a ceiling below the mechanical obstructions in the mechanical room and a full height door is to be installed for the shower. The sidewall head in the garage has been relocated. Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro4/26/20064/27/20064/27/2006APART
DetailsTroy Cobbley
3rd and 2nd floor piping can be covered. The ground floor piping can not. The sprinkler issues on the ground floor include: the pendant head in the master bath is not providing adequate coverage for the shower area. There is shadowing and the pendant measures 11'-8" off of the far wall in the shower, the sidewall head in the garage is overspaced off of the west wall. This entire wall is a separation of the living space from the garage. It measures 8'-7" off the wall and is not an extended coverage head. The pendant in the mechanical room is going to be blocked by duct work.