Permit Information
Permit NumberFIR06-00213
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 11333 W EXECUTIVE DR
Project NameSPR UG MERCHANTS MOVING
Customer Number 
ePlanReview 
Description
MERCHANTS MOVING - WAREHOUSE #4 - To install approximately 441 feet of 6" C-900 PVC connected in W. Executive Drive, running south 317 feet then east into an outside sprinkler valve room attached to a new 18,250-ft/2, one story warehouse and dock building. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD05-02379.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/18/20068/21/20068/21/2006APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection8/17/20068/18/20068/18/2006PCANC
DetailsTroy Cobbley
The fire alarm system was not ready to final yet
INSP-Sprinkler Rough-in/Hydro8/17/20068/17/20068/17/2006PPASS
DetailsTroy Cobbley
Underground hydro test passed.
INSP-Sprinkler Rough-in/Hydro8/11/20068/14/20068/14/2006ADONE
DetailsTroy Cobbley
Began the 24 hour air test at 10:00am. The left system is at 41psi and the right system is at 40 psi.
INSP-Supply line flush7/27/20067/28/20067/28/2006APART
DetailsForrest France
UG fire supply line flush performed satisfactory.
INSP-Sprinkler Rough-in/Hydro5/22/20065/22/20065/22/2006PPART
DetailsForrest France
The remainder of UG fire supply line including the ductile riser stub is approved for cover.
INSP-Sprinkler Rough-in/Hydro5/19/20065/22/20065/22/2006ACANC
DetailsTroy Cobbley
Contact: Jason - UG Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in5/18/20065/18/20065/19/2006PPART
DetailsTroy Cobbley
Roughly half of the long run of 8" underground is ok to cover. The other half including the 90's has not been installed yet.
INSP-Sprinkler Rough-in5/15/20065/18/20065/18/2006ACANC
DetailsTroy Cobbley
rescheduled for afternoon