Permit Information
Permit NumberFIR06-00258
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 101 S CAPITOL BLVD Unit: 1600
Project Namealm - US BANK-16TH FLR
Customer Number 
ePlanReview 
Description
To provide total notification in the remodeled TI space located on the 16th floor. Five new notification appliances (speaker/strobes) are being added to new common areas and one existing appliance will be changed to a 95 cd speaker/strobe. The existing fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown, fire/smoke damper control, door release and notification throughout. (This is a highrise, voice/evac is required).

The building permit BLD06-00258 is to remodel a 9,519 sq.ft. office area located on the 16th floor per approved plans. Work to include, selective interior nonbearing demolition, construction of new noncombustible partitions to create individual office spaces, breakroom, small conference rooms, reception area, and open office areas, installation of a new suspended ceiling system related lighting, miscellaneous related interior finishes. This building is fully fire sprinklered any alterations to the sprinkler system shall be per NFPA #13 as regulated by the fire department.. Rmh PER UNICO EXCEMPT BECAUSE THEY ARE THE PROPERTY OWNER OF US BANK PLAZA 3/7/06/MLS (QUANE SMITH)(US BANK-16TH FLR)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/4/20068/7/20068/7/2006PPASS
DetailsForrest France
Required corrections have been made, final fire alarm inspection passed.
INSP-Final Inspection8/1/20068/2/20068/3/2006AFAIL
DetailsForrest France
Notification device in the library is missing.
INSP-Alarm Testing6/27/20066/28/20066/28/2006PPART
DetailsForrest France
Inspection of alarm devices in phase two of the remodeled floor area are acceptable, still need to install one missing notification device in the west corridor as circled on plans and test phase 3 of the floor remodel when completed.
INSP-Alarm Testing5/15/20065/18/20065/18/2006APART
DetailsForrest France
Alarm tested satisfactory for the west portion of the project, need to add one notification device at area lacking coverage as marked on approved plans, the remainder of alarm work for the east half of the floor is not yet completed.