Permit Information
Permit NumberFIR06-00287
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 950 W BANNOCK ST Unit: 630
Project NameSPR ADVANCED SYS BANNER #630
Customer Number 
ePlanReview 
Description
ADVANCED SYSTEMS GROUP - BANNER BANK BLDG - STE 630 * This building is fire sprinklered because it is a high-rise. To add 6 SSP's and relocate 2 existing SSP's for the construction of a new 1,475-ft/2 office tenant space located on the 6th of a 182,950-ft/2, twelve story concrete and steel framed office and retail, w/parking, high rise building. Fire sprinkler work is related to the installation of "Nordwall" demountable nonbearing partitions with disallowed use of the "Room Design Method" (NFPA 13-11.2.3.3). The access floor system and the suspended ceilings were installed under permit BLD05-02939. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The shell fire sprinkler permit was installed under FIR05-00594. This permit is attached to building permit BLD06-00320.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/26/20065/31/20065/30/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Sprinkler Rough-in5/22/20065/23/20065/23/2006PFAIL
DetailsForrest France
Two heads as installed in the NE room of the tenant area are overspaced from an adjacent wall, also need to provide as-builts reflecting two deleted heads.