Project NameSPR SCOTTSDALE HOMES
Customer Number 
ePlanReview 
Description
SCOTTSDALE HOMES - To install a (modified) life safety NFPA 13D system in a five bedroom, three and half bathroom 4,438-ft/2 one story, single family dwelling (2758-ft/2 first floor, 1680-ft/2 second floor) with a attached 1056-ft/2 three car garage and 370-ft/2 basemen storage area. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (both installed by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-01869.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/16/200611/17/200611/17/2006APASS
DetailsForrest France
Fire sprinkler final inspection passed, permit finaled.
INSP-Final Inspection11/16/200611/16/200611/16/2006PPART
DetailsForrest France
UG flush completed, need to install missing head in the basement hall, calc. stickers, lock control valves open, provide annual inspection tag.
INSP-Final Inspection11/13/200611/15/200611/15/2006AFAIL
DetailsTroy Cobbley
Contractor was not ready for flush. The only items I inspected was the sprinkler heads. The head in the utility room is blocked by the light fixture. Many heads have been added. I told brian that he needs to provide as-builts to the returning inspector
INSP-Sprinkler Rough-in/Hydro5/23/20065/24/20065/24/2006PPART
DetailsForrest France
Overhead fire sprinkler is approved for cover.
INSP-Sprinkler Rough-in5/23/20065/23/20065/23/2006PFAIL
DetailsForrest France
One head at the 1st floor dining area is too close to a heat diffuser, two heads in the master bath 1st floor do not meet min. separation distances required, two drops are not installed in the main level bedroom, be aware of possible light fixture obstructions that may develop after fixture installation, one drop is missing in the basement hall, the supply, BFP, and riser are not installed at this time. Tenting for cold cavity protection appears adequate.