INSP-Final Inspection | 11/6/2006 | 11/7/2006 | 11/7/2006 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, missing outside bell sign installed while on site, shell sprinkler work passed final inspection.
|
INSP-Final Inspection | 11/3/2006 | 11/6/2006 | 11/6/2006 | A | DEFR |
Forrest France
|
|
|
Pending alarm permit final.
|
INSP-Final Inspection | 11/3/2006 | 11/3/2006 | 11/3/2006 | P | CANC |
Forrest France
|
|
|
Contact: Todd K; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley
|
INSP-Final Inspection | 11/1/2006 | 11/2/2006 | 11/2/2006 | A | DEFR |
Forrest France
|
|
|
Pending unfinished alarm work.
|
INSP-Sprinkler Rough-in/Hydro | 10/30/2006 | 10/31/2006 | 10/31/2006 | A | PART |
Forrest France
|
|
|
AG hydrostatic test for the two wet systems passed, noted to contractor the FDC piping will need to be hydro tested as well.
|
INSP-Sprinkler Rough-in/Hydro | 10/30/2006 | 10/30/2006 | 10/30/2006 | P | CANC |
Troy Cobbley
|
|
|
wrong inspection called in
|
INSP-Sprinkler Rough-in | 10/9/2006 | 10/10/2006 | 10/10/2006 | P | PASS |
Troy Cobbley
|
|
|
Forward flush of the backflow preventor passed. Rough-in inspection for the first and second floors passed. One additional EQ brace is needed at 4" second floor main in the northeast corner.
|
INSP-Sprinkler Rough-in | 9/15/2006 | 9/15/2006 | 9/15/2006 | P | PASS |
Troy Cobbley
|
|
|
The sprinkler piping above the hardlids on the second floor are ok to cover. This includes the hardlid 1/3 of the way up the north facing stairs.
|