Permit Number | FIR06-00381 |
Status | Finaled |
Name |
SIMPLEX/GRINNELL
|
Site Address |
1450 S LOGGERS POND PL
|
Project Name | alm - |
Customer Number | |
ePlanReview | |
Description |
To provide synchronization and visual notification in the ADA apartments. There are four buildings, three are in the Phase 1 configuration (FA0.1) and a single building in the Phase 2 configuration (FA0.2). Voltage drop calculations include visuals on both NAC circuits, only a single NAC circuit (A1) is shown with visual notification per the plans and riser. Battery calculations appear to be sufficient. Provide building map, including any architectural changes to the PDS Fire Inspector at time of inspection.
There is no associated building permit.
|