Permit Information
Permit NumberFIR06-00450
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 190 E BANNOCK ST
Project NameSPR ST LUKES 3C
Customer Number 
ePlanReview 
Description
ST LUKES-3C * To remodel within a 2,651-ft/2 portion of the existing administrative support office area on the 3rd floor of the Central Wing. Fire sprinkler work is related to selective demolition of interior non-bearing walls which includes utilities serving area and the construction of interior non-combustible walls to re-establish exit access corridor, create private offices, a conference room, locker room, one restroom and new suspended ceiling grid system. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit, to provide witness of compliance verification of meeting minimum code. This permit is attached to building permit BLD06-01193.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/26/200610/27/200610/27/2006APASS
DetailsForrest France
Required corrections have been verified for completion, permit finaled.
INSP-Sprinkler Rough-in10/20/200610/23/200610/23/2006AFAIL
DetailsForrest France
Four heads in the confrence room are supplied by a one inch line which appears to exceed the allowable calcs for this area, one area as marked on approved plans is not ready for inspection at this time.