Permit Number | FIR06-00454 |
Status | Finaled |
Name |
NORTHWEST SALES COMPANY
|
Site Address |
950 W BANNOCK ST Unit: 210
|
Project Name | alm - 10TH & BANNOCK-2ND FLR |
Customer Number | |
ePlanReview | |
Description |
To provide total notification in the TI space located on the 2nd floor. No written comments. Battery, voltage drop and speaker calculations appear to be sufficient. Provide revised building map, including any architectural changes to the PDS Fire Inspector at time of inspection.
The associated building permit (BLD06-01340) is to create a 2,787 square foot office tenant space on the 2nd story of an existing high-rise building. Work is to include Nordwall demountable partitions, interior nonrated doors, glass sidelights, and a new fire rated door in the 1-hr corridor wall. The access floor system and the suspended ceilings were installed under permit BLD05-02939. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (RCE-8247 THE CHRISTENSEN CORPORATION) (THE NATURE CONSERVANCY & GLOBAL FIRE INITIATIVE - BANNER BANK - STE 210)
|