Permit Information
Permit NumberFIR06-00461
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3083 S BOWN WAY
Project NameSPR CASA MEXICO
Customer Number 
ePlanReview 
Description
CASA MEXICO- BOWN CROSSING MARKET PLACE - BLDG E * to modify and existing shell system for a new 3,250-ft/2 restaurant tenant occupying the entire vacant first floor in an existing 6,500-ft/2 two story shell building. Shell building was done under BLD03-02288. Shell sprinklers were done under FIR04-00214. Fire sprinkler work is related to new interior walls, two new restrooms, a kitchen, a new walk-in cooler, two new Type I hoods. This building is fully fire sprinklered for occupancy separation reduction, fire flow, and story increase per the shell permit. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. This permit is attached to building permit: BLD06-00293.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/6/200610/6/200610/6/2006APASS
DetailsTroy Cobbley
Items on correction notice have been corrected.
INSP-Sprinkler Rough-in/Hydro9/22/20069/22/20069/22/2006AFAIL
DetailsForrest France
Two heads at the back exit near the riser exceed min. spacing, missing orfice at the inspectors test connection, the electrical/telephone closet will require walls extended to the deck for upright protection or provide a drop ceiling and pendent head. The remainder of drop ceiling areas are good for cover.