Permit NumberFIR06-00510
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 13901 W WAINWRIGHT DR
Project NameSPR UG CALM OFFICE BLDG SHELL
Customer Number 
ePlanReview 
Description
CALM OFFICE BUILDING (SHELL) UG - To install 30'-0" of 6" C-900 PVC underground for the fire sprinkler protection system in a new 10,958-ft/2, Type V-B fully fire sprinkled office building shell with 7 possible tenant spaces. Fire Sprinklers used for area. Separate plans and permits required for the overhead system. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD06-00102.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/16/20072/16/20072/16/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Supply line flush8/16/20068/17/20068/18/2006PPASS
DetailsTroy Cobbley
Underground flush passed.
INSP-Sprinkler Rough-in/Hydro7/27/20067/28/20067/28/2006APART
DetailsForrest France
UG hydrostatic test is acceptable.
INSP-Sprinkler Rough-in7/24/20067/24/20067/24/2006PPASS
DetailsTroy Cobbley
Underground piping is ok to cover.