INSP-Final Inspection | 3/1/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
Forrest France
|
|
|
FA permit finaled.
|
INSP-Final Inspection | 2/28/2007 | 3/1/2007 | 3/1/2007 | P | PASS |
Forrest France
|
|
|
c/n items verified for compliance, fire alarm permit finaled.
|
INSP-Final Inspection | 2/28/2007 | 2/28/2007 | 2/28/2007 | P | CANC |
Forrest France
|
|
|
Forest,
Could you close this permit?
Thanks,
Rob Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 9/1/2006 | 9/1/2006 | 9/1/2006 | A | PART |
Forrest France
|
|
|
Final pending completion of elevator controls and duct detectors for HVAC unit shutdown, required corrections from previous inspection have been completed.
|
INSP-Final Inspection | 8/29/2006 | 8/30/2006 | 8/30/2006 | P | PART |
Forrest France
|
|
|
Provide signage at the door to the FACP room, provide lock at the panel breaker, duct detectors for HVAC unit shutdown are not completed for testing, elevator is not installed (associated devices not tested). Control panel, pull stations, ID detectors for fire dampers, and notification devices for the 1st floor tested okay.
|
INSP-Final Inspection | 8/29/2006 | 8/31/2006 | 8/29/2006 | P | CANC |
Forrest France
|
|
|
rob's phone Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|