INSP-Final Inspection | 5/21/2008 | 5/21/2008 | 5/21/2008 | P | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 5/20/2008 | 5/21/2008 | 5/21/2008 | A | PASS |
Forrest France
|
|
|
Resubmittals verified, permit okayed for final.
|
INSP-Final Inspection | 5/7/2008 | 5/9/2008 | 5/9/2008 | A | NR |
Forrest France
|
|
|
Missing resubmittal plan set as necessary for permit final.
|
INSP-Sprinkler Rough-in/Hydro | 5/7/2008 | 5/9/2008 | 5/7/2008 | A | CANC |
Forrest France
|
|
|
Phone #: ###-#### Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
|
FIR-Aging Inspection | 2/7/2008 | 2/8/2008 | 2/8/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit okay for final.
|
INSP-Sprinkler Rough-in/Hydro | 6/25/2007 | 6/26/2007 | 6/26/2007 | A | PASS |
Forrest France
|
|
|
Fire sprinkler system modifications passed inspection.
|
INSP-Final Inspection | 12/21/2006 | 12/22/2006 | 12/26/2006 | P | FAIL |
Forrest France
|
|
|
Project work is not ready for final as requested due to missing ceilings, ceiling tile, escutcheons, safety caps at some heads are not removed. The as-builts for system modifications made at the new stairway will not be accepted as the work performed exceeds the scope of changes allowed to be approved in the field. Submit documents showing modifications for plan review and approval prior to next inspection.
|