INSP-Final Inspection | 11/25/2008 | 11/26/2008 | 11/26/2008 | A | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Final Inspection | 11/24/2008 | 11/25/2008 | 11/25/2008 | A | DEFR |
Forrest France
|
|
|
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton
|
INSP-Final Inspection | 10/31/2008 | 11/4/2008 | 11/5/2008 | A | PART |
Forrest France
|
|
|
Reinspection for noted corrections regarding cleanroom area fire alarm notification (see activity notes 4/29) completed acceptable.
|
INSP-Alarm Testing | 10/8/2008 | 10/14/2008 | 10/14/2008 | A | PART |
Forrest France
|
|
|
UF heat detectors at the cleanroom areas tested acceptable, SD for door release at the north side okayed, two manual pulls and one heat detector at the service isle passed.
|
INSP-Alarm Testing | 10/3/2008 | 10/7/2008 | 10/7/2008 | A | PART |
Forrest France
|
|
|
Inspection completed for cleanroom area ceiling mounted heat detectors only, need to provide accurate addressing at plenum #5, install one missing junction box cover. Intelligent detectors not tested at this time.
|
INSP-Alarm Testing | 10/2/2008 | 10/2/2008 | 10/2/2008 | P | PART |
Forrest France
|
|
|
Tested remainder of SD at the 2nd floor ceilings including the mechanical and corridor areas, manual pull stations and (AC) smoke detectors at the west corridor tested okay, one added SD approved, duct detectors at the gas bunker passed. See plans for annotations.
|
INSP-Alarm Testing | 9/26/2008 | 9/30/2008 | 10/1/2008 | A | PART |
Forrest France
|
|
|
Tested remainder of smoke and heat detectors at the above ceiling areas noted on 1st floor drawings, see plans for locations of spot detectors at the 2nd floor ceiling tested today marked in green, noted overspaced area at the NE corner, inspection completed on 9/30 (PM).
|
INSP-Alarm Testing | 6/25/2008 | 6/26/2008 | 6/26/2008 | A | CANC |
Forrest France
|
|
|
Overbooked
|
INSP-Alarm Testing | 6/16/2008 | 6/18/2008 | 6/18/2008 | A | PART |
Forrest France
|
|
|
See locations marked on plan set for heat and smoke detection devices (AC's) tested today at the second floor mechanical level.
|
INSP-Alarm Testing | 5/27/2008 | 5/30/2008 | 5/30/2008 | A | CANC |
Forrest France
|
|
|
Please call 30 min. prior to arrival Phone #: ###-#### Internet Inspection Request from: Jeff Walton Overbooked
|
INSP-Alarm Testing | 5/12/2008 | 5/14/2008 | 5/14/2008 | A | PART |
Forrest France
|
|
|
Testing for the second floor AHU duct detectors completed okay as noted on plans with the exception of address changes at three locations and sample tubes to be extended as necessary for red-lined locations.
|
INSP-Alarm Testing | 4/23/2008 | 4/29/2008 | 4/29/2008 | A | PART |
Forrest France
|
|
|
Horn and strobe testing completed for the cleanroom areas only, noted locations on plan in need of revision.
|
INSP-Alarm Testing | 4/23/2008 | 4/28/2008 | 4/28/2008 | A | PART |
Forrest France
|
|
|
Completed preliminary walkthrough of cleanroom areas prior to fire alarm notification test to verify positioning, cd settings and spacing of horn/strobe appliances.
|
INSP-Alarm Testing | 3/31/2008 | 4/2/2008 | 4/1/2008 | A | CANC |
Forrest France
|
|
|
Will call in inspection for next week when.KR
|
INSP-Alarm Testing | 1/30/2008 | 2/1/2008 | 1/30/2008 | A | CANC |
Forrest France
|
|
|
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
|
INSP-Alarm Testing | 1/28/2008 | 1/29/2008 | 1/29/2008 | A | PART |
Forrest France
|
|
|
Tested horn strobe notification devices for the second floor mechanical and electrical room areas including the penthouse mech. except as noted per annotations (circut 52 and the 2nd floor corridor, noted one area lacking sufficient coverage, need weatherproof back box for the h/s at the roof deck, noted cd ratings on the as-built plans are not accurate to the field install at some locations, audibility is satisfactory.
|
INSP-Alarm Testing | 1/17/2008 | 1/24/2008 | 1/24/2008 | A | CANC |
Forrest France
|
|
|
Please call 30 min prior to arrival Phone #: ###-#### Internet Inspection Request from: Jeff Walton
|
INSP-Alarm Testing | 1/17/2008 | 1/23/2008 | 1/23/2008 | A | CANC |
Forrest France
|
|
|
Please call 30 min prior to arrival Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
|
INSP-Alarm Testing | 1/17/2008 | 1/22/2008 | 1/22/2008 | A | PART |
Forrest France
|
|
|
Reinspection for defficient items at last site visit completed okay, see as-built plans for areas inspected today, noted one address change and two additonal SD to be added due to overspacing.
|
INSP-Alarm Testing | 11/13/2007 | 11/15/2007 | 11/16/2007 | A | PART |
Forrest France
|
|
|
See as-built plans marked for areas inspected today and noted items in need of revision including door release, adding SD at an electrical room, relocating three SD at the gas bunker, will review approved plans at the next scheduled visit.
|
FIR-Aging Inspection | 3/13/2007 | 3/13/2007 | 3/16/2007 | | DONE |
Forrest France
|
|
|
work in progress
|