INSP-Final Inspection | 1/25/2007 | 1/25/2007 | 1/25/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Conference | 1/17/2007 | 1/17/2007 | 1/18/2007 | P | DONE |
Troy Cobbley
|
|
|
alan is working on the permanant heat issue
|
INSP-Final Inspection | 1/15/2007 | 1/16/2007 | 1/16/2007 | A | FAIL |
Troy Cobbley
|
|
|
Provide correct backflow or data sheet proving friction loss as calculated has not been exceeded. Provide forward flush. Provide permanant heat, insulation above ceiling in the riser room and provide a one hour rated room.
|
INSP-Sprinkler Rough-in/Hydro | 1/11/2007 | 1/12/2007 | 1/12/2007 | A | PASS |
Troy Cobbley
|
|
|
overhead hydro and roughin passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/9/2007 | 1/10/2007 | 1/10/2007 | A | FAIL |
Troy Cobbley
|
|
|
The attic sprinkler heads are too close to the deck and a high temp pendant will be required above the unit heater. Hydro test failed due to loss of pressure and now the changes in the attic heads that is required.
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/9/2007 | 1/9/2007 | P | CANC |
Troy Cobbley
|
|
|
To be rescheduled
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 1/8/2007 at 9:46:53 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Jan 8 2007 10:44AM.
|
FIR-Aging Inspection | 12/27/2006 | 12/27/2006 | 12/27/2006 | | NR |
Troy Cobbley
|
|
|
work is in progress
|