Permit Information
Permit NumberFIR06-00639
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 412 S 13TH ST
Project NamePlaza Mixed Use-Residential
Customer Number 
ePlanReview 
Description
Under this permit, provide complete sprinkler coverage from the first level through out the fifth floor. (Section 1 of 2). The wet pipe system will be supplied from a wet combination class I standpipe sprinkler riser. Each floor will be controlled from a local sectional control valve with exception to the fifth floor sectional control valve which will be controlled from the forth floor stair well, independent from the fifth floor. The Underground and the Garage level work has been permitted under separate permits.
This permit is attached to BLD05-02204 for the Plaza Mixed Used - (Section 1 of 2) A two hour fire wall (also use as a horizontal exit) will be constructed to divide this 42 unit, 61,812 sq.ft. 5 story, wood framed apartment building into two separate buildings, above a Type I-A parking garage, per City Ordinance 4-16. This portion of the building contains 25 units, and is 36,048 which 1,281 sq. ft. is occupied roof area. There are two of these units that are less than 800 sq.ft. each. Refer to BLD 05-02750 for the other side of the fire wall. Refer to BLD 05-00926 & FIR06-00365 for the parking garage. Refer to BLD 06-00693 for the north building. NOTE: This building is fully fire sprinklered per NFPA 13 per Boise City Ordinance. All construction per the approved plans and attached comment list. MJP DRH 04-00241 CUP 04-00087.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/1/20075/1/20075/1/2007PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection4/23/20074/24/20074/24/2007AFAIL
DetailsForrest France
Noted several items in need of correction prior to final including painted heads at various locations, missing flex couplings at the standipe risers in the stairwells, mixed head types in the south stairway, missing escutcheons at some locations, leaking head at the model unit bathroom, forward flow completed okay, missing automatic ball drip at the FDC check, need to test AFS monitoring as well.
INSP-Sprinkler Rough-in/Hydro3/16/20073/19/20073/19/2007APART
DetailsForrest France
Hydrostatic test of the OH main and standpipes completed satisfactory.
INSP-Sprinkler Rough-in/Hydro3/6/20073/6/20073/6/2007PPART
DetailsForrest France
OH hydrostatic test for the basement level parking garage system and the 1st level garage access ramp fire sprinkler piping completed okay.
INSP-Sprinkler Rough-in/Hydro1/2/20071/3/20071/3/2007APART
DetailsForrest France
AG hydrostatic test for the garage area first level passed.
INSP-Supply line flush12/29/20061/2/20071/2/2007APASS
DetailsTroy Cobbley
Underground flush passed
INSP-Sprinkler Rough-in11/27/200611/28/200611/28/2006APART
DetailsForrest France
Corrections for the 2nd floor rough-in are complete, overhead sprinkler is approved for cover.
INSP-Sprinkler Rough-in11/27/200611/27/200611/27/2006PFAIL
DetailsForrest France
2nd floor OH sprinkler install needs correction in some areas as indicated on approved plan set including locations where heads are spaced too close, hangers are missing, one head needs to be removed, the sw heads at the patio areas are not yet installed. The 1st floor overhead install at the apartments only is approved for cover.
INSP-Sprinkler Rough-in/Hydro11/21/200611/22/200611/22/2006APART
DetailsForrest France
1st floor hydro test okay.
INSP-Sprinkler Rough-in/Hydro11/20/200611/21/200611/21/2006APART
DetailsForrest France
AG hydrostatic test of the 2nd floor passed.
INSP-Sprinkler Rough-in/Hydro11/17/200611/20/200611/20/2006AFAIL
DetailsForrest France
AG hydrostatic test not ready at this time due to system leakage to be repaired today per contractor.
INSP-Sprinkler Rough-in11/16/200611/16/200611/17/2006PPART
DetailsForrest France
Need to provide correct as-builts reflecting actual installation of overhead piping for the 3rd floor previous to approval for cover.
INSP-Sprinkler Rough-in/Hydro11/14/200611/15/200611/14/2006APASS
DetailsForrest France
OH hydrostatic test of the 3rd floor is acceptable.
INSP-Sprinkler Rough-in/Hydro11/9/200611/13/200611/13/2006ANR
DetailsForrest France
OH hydrostatic test of the 3rd floor is not ready. 1st floor rough-in of the model unit for cover is okay. Discussed DSW locations at the 3rd floor canopies.
INSP-Sprinkler Rough-in11/3/200611/3/200611/3/2006PPART
DetailsForrest France
The 5th and 4th floors are approved for cover as noted on job shack plan set.
INSP-Sprinkler Rough-in/Hydro10/27/200610/30/200610/30/2006APART
DetailsForrest France
OH hydrostatic test for the 4th floor passed, items noted on previous c/n for the 4th floor have been completed.
INSP-Sprinkler Rough-in10/25/200610/26/200610/26/2006APART
DetailsForrest France
OH rough-in inspection for the 4th floor completed today. Noted elevator and garbage chute piping to heads at these locations is not yet complete, one W.D closet needs is missing a SW head, one pendent in a mec. closet is too close to the wall and blocked by ductwork, the provided as-built plans match the installation except as annotated.
INSP-Sprinkler Rough-in10/16/200610/16/200610/16/2006PFAIL
DetailsForrest France
Inspection for the 5th floor rough-in only, one head as installed is overspaced as marked on approved plans, need to provide documentation that roofing insulation is sufficient to provide adequate freeze protection for overhead piping run in the joist channels at the deck, will need plan review verification that unsprinklered water closets are acceptable for this NFPA 13 system, overhead hydro for the 5th floor is okay, some field modifications have been made which deviate from the approved set of drawings.