Permit Information
Permit NumberFIR06-00672
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 330 N MILWAUKEE ST
Project NameTHE CHEESECAKE FACTORY BTS
Customer Number 
ePlanReview 
Description
Cheesecake Factory at Boise Towne Square - To construct a 9,488 sq. ft. restaurant with and fenced in storage/equipment area on the south side of the Boise Towne Square Mall. Building is a 9,488 sq. ft. one story Type IIB fully fire sprinkled with no openings into the existing mall building. Other work includes all site improvements, landscaping and paving per approved plans and attachments, DRH04-00219Mod # 2. Fire sprinklers are used for an unlimited area mall building. This building including the new addition is to maintain 60 foot open yards. The sprinkler scope includes spinkling through out the tenant space with exception to the tower above the main entry. The existing 6" underground service was installed under a separate permit FIR06-00662.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/24/200611/24/200611/24/2006PPASS
DetailsTroy Cobbley
Permit finaled. Forward flush passed.
INSP-Final Inspection11/21/200611/22/200611/22/2006AFAIL
DetailsTroy Cobbley
relocate bell to the fdc location
INSP-Sprinkler Rough-in/Hydro11/20/200611/21/200611/21/2006APASS
DetailsTroy Cobbley
Above ground hyro test pased on the third try. Unable to start alarm test.
INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006PPART
DetailsForrest France
Inspection for a portion of the drop ceiling areas at the main seating area and the kitchen prep. hallway are okay for cover, several pendent heads at scattered locations are not yet installed.
INSP-Sprinkler Rough-in10/26/200610/26/200610/26/2006PPART
DetailsForrest France
OH rough-in is okay to cover at the hard lid ceilings. Heads in the drop ceilings, UG supply and the riser are not completed.
INSP-Sprinkler Rough-in10/23/200610/23/200610/23/2006PPART
DetailsForrest France
Partial inspection for the OH rough-in due to several areas not completed, missing EQ bracing at the end main, FDC and top of riser, drops are not installed at some locations, main and branch line installation is acceptable, noted areas at columns and soffits which may present obstructions, 130ft2 spacing to be verified when heads are cut in, UG supply and riser are not completed at this time.