Permit Information
Permit NumberFIR06-00686
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 350 N MILWAUKEE ST Unit: 2154
Project NameSun Glass Hut -BTS - #2154
Customer Number 
ePlanReview 
Description
To remodel an existing 1,254 sq.ft. retail space on the upper level of the existing covered mall per approved plans. Work to include, construction of a storefront system with new security grill, construction of an accessible restroom, construction of a new noncombustible partition, installation of new suspended ceiling system and related lighting, miscellaneous related interior finishes. This building is fully fire sprinklered and contains a smoke evacuation system, any alterations or modifications to the sprinkler system shall be per NFPA #13. The smoke evacuation system shall remain operational as originally installed under the 1985 UBC. Treasure Valley Fire Protection to install 17 new semi-recessed SSP's throughout the new tenant space and 3 new concealer type heads in the bulkhead entry.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/19/200610/20/200610/20/2006APASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection10/17/200610/18/200610/18/2006AFAIL
DetailsTroy Cobbley
sprinkler canopies are missing and ceiling tiles are missing.
INSP-Sprinkler Rough-in10/12/200610/12/200610/13/2006PPART
DetailsTroy Cobbley
Sprinkler piping is ok to cover but one additional head is needed in the front display area due to a horizontal obstruction and the wood supporting the hvac unit is a problem