INSP-Final Inspection | 4/6/2007 | 4/10/2007 | 4/10/2007 | A | PASS |
Forrest France
|
|
|
Fire sprinkler finaled, noted one standard response head to be replaced with a QR as discussed.
|
INSP-Final Inspection | 4/4/2007 | 4/9/2007 | 4/9/2007 | A | PART |
Forrest France
|
|
|
Okay for final when ceiling tile and escutcheons are complete.
|
INSP-Sprinkler Rough-in/Hydro | 4/4/2007 | 4/6/2007 | 4/6/2007 | A | PART |
Forrest France
|
|
|
OH fire sprinkler rough-in at 103 B4 is approved for cover, final pending ceiling tile and escutcheons.
|
INSP-Sprinkler Rough-in/Hydro | 3/22/2007 | 3/26/2007 | 3/26/2007 | A | PART |
Troy Cobbley
|
|
|
The sprinkler piping in room 106A is ok to cover. I verified the piping arrangement as shown on the drawing. This drawing is to be presented to Sam Rogers for sign off. The flow switch still needs to be installed. No alarms were tested.
|
INSP-Sprinkler Rough-in | 3/21/2007 | 3/22/2007 | 3/22/2007 | A | CANC |
Forrest France
|
|
|
drawings will be red lined Phone #: ###-#### Inspection cancelled from web by: Rob Puckett
|
INSP-Final Inspection | 3/15/2007 | 3/21/2007 | 3/21/2007 | A | FAIL |
Forrest France
|
|
|
Fire sprinkler installation at room 103 is not complete, heads and supply piping with control valve loop for chem. cabinet coverage are not shown on approved plans, room 106 cabinet loop is not indicated, OH pendents are not installed as reflected.
|