Description
Add & relocate down heads in space #2170 (Zumiez) to accommodate a new wall and ceiling layout. The work under this permit is limited to the tenant space only.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification. This permit is attached to BLD06-02572.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/20/200611/20/200611/20/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection11/14/200611/14/200611/14/2006PCANC
DetailsTroy Cobbley
Sprinkler heads have been painted so no inspection was done.
INSP-Sprinkler Rough-in11/7/200611/7/200611/7/2006PPART
DetailsForrest France
Overhead rough-in is acceptabe pending verification the original system design can support up to three heads off 1" pipe as newly installed at one loction in the front canopy area.