Permit Information
Permit NumberFIR06-00978
StatusFinaled
Name WESTERN STATES FIRE PROTECTION
Site Address 5434 N QUAIL SUMMIT WAY
Project Name 
Customer Number 
ePlanReview 
Description
To install a wet antifreeze system through out, in accordance with NFPA13D. The under ground supply is by other. This house shall be fitted with an NFPA 13D modified system to include barrier protection between the garage and the living spaces. The system shall also be equipped with an alarm initiating device commonly referred to as a flow switch, and an outside alarm indicating device. All fire sprinkler work and related, which includes, single service water supply, the system backflow prevention device shall be installed or under the license by a Fire Sprinkler Contractor in the State of Idaho, which shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to building permit BLD06-02290.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/18/20075/18/20075/18/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection5/16/20075/17/20075/18/2007PFAIL
DetailsTroy Cobbley
The plans have not been resubmitted as previously requested. no inspection performed
INSP-Sprinkler Rough-in1/17/20071/18/20071/18/2007APASS
DetailsTroy Cobbley
Fire sprinkler piping is ok to cover. Per the review comments the plans need to be resubmitted. With those resubmittals the contractor needs to show the pipe routing changes.