INSP-Final Inspection | 2/13/2008 | 2/13/2008 | 2/13/2008 | P | PASS |
Forrest France
|
|
|
Correction notice items are complete, fire sprinkler final inspection passed, permit finaled.
|
INSP-Final Inspection | 2/11/2008 | 2/12/2008 | 2/12/2008 | A | FAIL |
Forrest France
|
|
|
Need to remove travel caps and install escutcheons at each sprinkler head in the mechanical closets per unit.
|
INSP-Final Inspection | 2/6/2008 | 2/7/2008 | 2/7/2008 | P | FAIL |
Forrest France
|
|
|
Provide clearance at the riser/floor slab, missing sprinkler coverage at the riser, missing "911" sign at the bell, provide signage at the floor control valves indicating what system is served, missing orfice at the inspectors test, not all items for final reviewed at this time due to number of defficiencies found.
|
INSP-Sprinkler Rough-in | 6/7/2007 | 6/11/2007 | 6/11/2007 | P | PART |
Forrest France
|
|
|
Rough-in for building #2 is okay for cover, noted two areas where tenting needs to be adjusted-contractor to repair as agreed.
|
INSP-Sprinkler Rough-in/Hydro | 6/7/2007 | 6/11/2007 | 6/11/2007 | P | PART |
Forrest France
|
|
|
AG hydrostatic test for building #2 passed.
|
INSP-Sprinkler Rough-in | 6/6/2007 | 6/7/2007 | 6/7/2007 | A | DEFR |
Forrest France
|
|
|
Inspection rescheduled in conjunction with an OH hydro on 6/11 per phone call from contractor.
|
INSP-Sprinkler Rough-in | 6/5/2007 | 6/6/2007 | 6/6/2007 | P | CANC |
Troy Cobbley
|
|
|
No time for rough-in inspection due to time constraints. Jeff stated he would call it back in.
|
INSP-Supply line flush | 6/5/2007 | 6/6/2007 | 6/6/2007 | P | PASS |
Troy Cobbley
|
|
|
UG flush passed
|
INSP-Supply line flush | 4/17/2007 | 4/18/2007 | 4/18/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed satisfactory at the west building riser, also approved garage areas for cover as corrections have been made.
|
INSP-Sprinkler Rough-in/Hydro | 4/11/2007 | 4/12/2007 | 4/12/2007 | A | NR |
Forrest France
|
|
|
Lacking water supply for line flush.
|
INSP-Sprinkler Rough-in/Hydro | 4/9/2007 | 4/11/2007 | 4/11/2007 | A | CANC |
Forrest France
|
|
|
Flush - Contact: Jeff Chaney
Phone #: ###-#### x1234 Inspection cancelled from web by: Alicia Pauley
|
INSP-Sprinkler Rough-in/Hydro | 1/24/2007 | 1/25/2007 | 1/25/2007 | A | PART |
Forrest France
|
|
|
UG fire supply line is approved for bury.
|