Permit Information
Permit NumberFIR06-00985
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 2233 E WARM SPRINGS AVE
Project NameFALLINGBROOK CONDOS
Customer Number 
ePlanReview 
Description
To construct a new 13,676 sq. ft., two story, ten unit, apartment building. An NFPA 13R fire sprinkler system is required in each unit. NOTE: Each unit is over 800 sq. ft. Each unit is separated from adjoining unit by a 1-hour fire partition extending from top of foundation to tight against the bottom of the roof deck. This structure will be fire sprinklered through out the living space. System shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes dual service underground water supply, the system backflow prevention device (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-01994.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/13/20082/13/20082/13/2008PPASS
DetailsForrest France
Correction notice items are complete, fire sprinkler final inspection passed, permit finaled.
INSP-Final Inspection2/11/20082/12/20082/12/2008AFAIL
DetailsForrest France
Need to remove travel caps and install escutcheons at each sprinkler head in the mechanical closets per unit.
INSP-Final Inspection2/6/20082/7/20082/7/2008PFAIL
DetailsForrest France
Provide clearance at the riser/floor slab, missing sprinkler coverage at the riser, missing "911" sign at the bell, provide signage at the floor control valves indicating what system is served, missing orfice at the inspectors test, not all items for final reviewed at this time due to number of defficiencies found.
INSP-Sprinkler Rough-in6/7/20076/11/20076/11/2007PPART
DetailsForrest France
Rough-in for building #2 is okay for cover, noted two areas where tenting needs to be adjusted-contractor to repair as agreed.
INSP-Sprinkler Rough-in/Hydro6/7/20076/11/20076/11/2007PPART
DetailsForrest France
AG hydrostatic test for building #2 passed.
INSP-Sprinkler Rough-in6/6/20076/7/20076/7/2007ADEFR
DetailsForrest France
Inspection rescheduled in conjunction with an OH hydro on 6/11 per phone call from contractor.
INSP-Sprinkler Rough-in6/5/20076/6/20076/6/2007PCANC
DetailsTroy Cobbley
No time for rough-in inspection due to time constraints. Jeff stated he would call it back in.
INSP-Supply line flush6/5/20076/6/20076/6/2007PPASS
DetailsTroy Cobbley
UG flush passed
INSP-Supply line flush4/17/20074/18/20074/18/2007APART
DetailsForrest France
UG fire supply line flush completed satisfactory at the west building riser, also approved garage areas for cover as corrections have been made.
INSP-Sprinkler Rough-in/Hydro4/11/20074/12/20074/12/2007ANR
DetailsForrest France
Lacking water supply for line flush.
INSP-Sprinkler Rough-in/Hydro4/9/20074/11/20074/11/2007ACANC
DetailsForrest France
Flush - Contact: Jeff Chaney
Phone #: ###-#### x1234 Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro1/24/20071/25/20071/25/2007APART
DetailsForrest France
UG fire supply line is approved for bury.