Permit Information
Permit NumberFIR07-00015
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project NameSLRMC IN-PATIENT PHARMACY
Customer Number 
ePlanReview 
Description
This permit is to install a new notification extender panel, associated NAC circuits and visual appliances. The addition of a new addressable signal line circuit #5 and associated smoke and heat detectors to a Honeywell FS-90 fire alarm control panel. Total area coverage in the corridors and within the tenant space will be used to release the fire smoke/dampers and door hold open devices. Building Permit BLD06-02762 is to remodel a 5,847 sq. ft. portion of the sub-basement of SLRMC to be used as and in support of the IN-PATIENT Pharmacy. Work involves two separate area and is divided into four phases for the purpose of continuing operations of services within the area as portion are upgraded and then reoccupied. Work involves selective non-structural demolition; maintenance of existing fire-resistive rated construction; interior non-combustible, fire-resistive wall construction to create admin offices, tech work stations, preparations and storage areas of pharmacy medicines. To upgrade electrical, mechanical, plumbing, sprinkler alarm cabinetry and finishes throughout the remodeled area to meet tenant needs and provide compliance with current adopted codes and ordinances. Drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/27/20095/28/20095/28/2009APASS
DetailsForrest France
Remainder of fire alarm work passed functional testing, permit approved for final status.
INSP-Alarm Testing8/30/20079/4/20079/4/2007APART
DetailsForrest France
See approved plans for areas tested today, noted some floor plan modifications affecting alarm work, need to add devices as noted, addressing has changed at some locations and is recorded on as-builts.
INSP-Alarm Testing8/29/20078/30/20078/30/2007ACANC
DetailsForrest France
Overbooked
INSP-Alarm Testing8/30/20079/4/20078/30/2007ACANC
DetailsForrest France
Forrest,
This is a confirmation of rescheduling a partial inspection of in-patient pharmacy at St. Luke''s Hospital from today to next Tuesday, 9-4-07 due to inspection backlog. Please call for time.
Thanks,
Jim Phone #: ###-#### Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
INSP-Alarm Testing3/7/20073/8/20073/8/2007APART
DetailsForrest France
Fire alarm testing for the area north of the hallway as red lined on approved plans is satisfactory.