INSP-Final Inspection | 2/18/2008 | 2/19/2008 | 2/19/2008 | A | PASS |
Forrest France
|
|
|
Fire sprinkler permit finaled.
|
INSP-Final Inspection | 1/10/2008 | 1/11/2008 | 1/14/2008 | A | FAIL |
Forrest France
|
|
|
One head at the master bedroom is obstructed by an adjacent light fixture, one missing escutcheon installed while on site.
|
INSP-Final Inspection | 1/10/2008 | 1/10/2008 | 1/10/2008 | P | FAIL |
Forrest France
|
|
|
Painted heads have not been replaced, missing escutcheons at all areas.
|
INSP-Final Inspection | 12/14/2007 | 12/17/2007 | 12/17/2007 | A | FAIL |
Forrest France
|
|
|
As-built plans for this project were not provided.
|
INSP-Final Inspection | 11/30/2007 | 12/3/2007 | 12/3/2007 | A | FAIL |
Forrest France
|
|
|
Heads at two locations are missing/not installed, need as-built plans for floor plan and field changes.
|
INSP-Sprinkler Rough-in/Hydro | 10/25/2007 | 10/26/2007 | 10/29/2007 | P | PART |
Forrest France
|
|
|
Hydro test passed.
|
FIR-Aging Inspection | 6/14/2007 | 6/14/2007 | 6/14/2007 | | DONE |
Forrest France
|
|
|
Building under construction, work in progress.
|