Permit NumberFIR07-00098
StatusFinaled
Name BAUERLE ELECTRONICS
Site Address 809 E PENNSYLVANIA DR
Project Name809 Pennsylvania Dr (Assisted)
Customer Number 
ePlanReview 
Description
This permit includes modification to an existing fire alarm system that was installed in this residence. Modification includes tie in of a newly installed residential fire sprinkler system the addition of a hallway smoke detector and field inspection of code compliance for these systems.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/23/20072/26/20072/26/2007APASS
DetailsForrest France
Required corrections have been verified for completion, fire alarm permit finaled.
INSP-Final Inspection2/20/20072/20/20072/21/2007PFAIL
DetailsTroy Cobbley
Sound levels were not adequate in the sleeping areas.
INSP-Final Inspection2/14/20072/14/20072/14/2007PFAIL
DetailsTroy Cobbley
Contractor did not have smoke to test the detector and there was no water in the fire sprinkler system to test the flow switch. The tamper switches did operate however.