Permit Information
Permit NumberFIR07-00150
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1112 W MAIN ST Unit: 501
Project NameROYAL PLAZA
Customer Number 
ePlanReview 
Description
This TI in suite #501 includes dropping 23 residential heads into the new wall and ceiling layout of the dwelling unit. Also to add 4 other dry SSP & 3 dry SSU heads on the terrace. The work shall be performed in accordance with NFPA13R installation guidelines. This building is fully fire sprinklered for one-hour substitution. The fire sprinkler system work shall comply with IFC 2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD6-03518.
When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/16/20081/17/20081/17/2008APASS
DetailsForrest France
Fire sprinkler permit finaled, as-builts accepted.
INSP-Final Inspection1/10/20081/11/20081/14/2008APART
DetailsForrest France
Okay for final pending accurate as-built plans.
INSP-Final Inspection1/9/20081/10/20081/10/2008PNR
DetailsForrest France
Escutcheons have not yet been installed, project is not ready for final at this time.
INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007PDEFR
DetailsForrest France
See inspection notes under the shell permit.
INSP-Sprinkler Rough-in/Hydro10/25/200710/26/200710/29/2007PPART
DetailsForrest France
Hydro test passed.
INSP-Final Inspection8/22/20078/23/20078/23/2007AFAIL
DetailsForrest France
One head is blocked by ductwork at a mech. closet, pendent at the kitchen area must meet obstruction tables for proximity to an adjacent soffit, remainder of ceilings are okay for cover.
INSP-Sprinkler Rough-in8/16/20078/17/20078/17/2007ANR
DetailsForrest France
Pending light fixture obstruction issues.