Name COMMERCIAL FIRE PROTECTION
Site Address 2234 S BROADWAY AVE
Project NameShakoori Office Bldg'
Customer Number 
ePlanReview 
Description
Install fire sprinklers through out the existing structure. The underground service leading to the building was done by others. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD06-03008.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/11/20076/11/20076/11/2007PPASS
DetailsForrest France
Fire sprinkler passed final inspection, permit finaled.
INSP-Sprinkler Rough-in/Hydro3/18/20073/19/20073/19/2007APART
DetailsForrest France
OH hydrostatic test passed inspection.
INSP-Final Inspection3/18/20073/19/20073/19/2007APART
DetailsForrest France
OH rough-in is approved for cover, noted leaking 1/2" weld-o-let at the riser supply FLxGV piece, missing head box, outside bell, need ceilings and escutcheons and sprinkler supervision alarm testing prior to permit final.
INSP-Supply line flush3/18/20073/19/20073/19/2007APART
DetailsForrest France
UG supply line flush completed.