Permit Information
Permit NumberFIR07-00208
StatusFinaled
Name INTEGRATED SECURITY RESOURCES
Site Address 970 W RIVER ST
Project NameIDAHO RECORDS MGMNT
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a new fire sprinkler monitoring system and associated initiating devices with one notification appliance located in the building managers office and exterior outside bell. Building permit BLD06-01663 is to construct a new 12,745 square foot, one story addition to the east side of existing 33,000 square foot, two story storage and office building A/B. The new addition is identified as Building D. The required accessible restrooms are in building A/B. The new building addition is constructed of a pre-engineered metal building on a concrete slab floors and foundation. The office space and restrooms shown on the floor plan are future and are not approved as part of this permit. A separate permit will be required to finish those spaces. All construction shall be per the approved plans. JCM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/11/20077/12/20077/12/2007APASS
DetailsForrest France
Final corrections have been made, fire alarm work passed inspection, permit finaled.
INSP-Final Inspection7/10/20077/11/20077/11/2007AFAIL
DetailsForrest France
Still missing lock and paint at the breaker to the FACP, need to provide a horn only for the notification device in the office area, all other items tested satisfacory.
INSP-Final Inspection7/9/20077/10/20077/10/2007AFAIL
DetailsForrest France
Per fire code review notes items 2 and 5, need record of inspection and testing completed prior to final, supervisory signals shall be self restoring, missing lock at the FACP breaker, provide means to test phase reversal at the pump.
INSP-Final Inspection7/5/20077/6/20077/6/2007PFAIL
DetailsTroy Cobbley
No testing done since the panel was in a ground fault condition and was being worked on by the contractor.