INSP-Final Inspection | 7/11/2007 | 7/12/2007 | 7/12/2007 | A | PASS |
Forrest France
|
|
|
Final corrections have been made, fire alarm work passed inspection, permit finaled.
|
INSP-Final Inspection | 7/10/2007 | 7/11/2007 | 7/11/2007 | A | FAIL |
Forrest France
|
|
|
Still missing lock and paint at the breaker to the FACP, need to provide a horn only for the notification device in the office area, all other items tested satisfacory.
|
INSP-Final Inspection | 7/9/2007 | 7/10/2007 | 7/10/2007 | A | FAIL |
Forrest France
|
|
|
Per fire code review notes items 2 and 5, need record of inspection and testing completed prior to final, supervisory signals shall be self restoring, missing lock at the FACP breaker, provide means to test phase reversal at the pump.
|
INSP-Final Inspection | 7/5/2007 | 7/6/2007 | 7/6/2007 | P | FAIL |
Troy Cobbley
|
|
|
No testing done since the panel was in a ground fault condition and was being worked on by the contractor.
|