Permit Information
Permit NumberFIR07-00216
StatusFinaled
Name PROTEX
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
This permit is to add a remote NAC power supply, notification appliances and manual pull stations to an existing fire alarm system due to a 1st time tenant improvement. Building Permit # BLD07-00216 is to construct a first time tenant build-out of an 12,188 sq. ft. portion of the existing 17,745 sq. ft. second floor for use as an office by W & H Pacific per approved plans, to include red-lined plan review comments on plan sheets and all attached plan review comments & conditions of all reviewing agencies as part of the approved plans, requiring compliance & verification for final occupancy approval. There is an existing central core to this building, approximately 780 sq. ft., which includes the three exit stair systems; and an elevator for accessibility compliance, part of BLD06-00688. Accessible restrooms to serve all tenants on this floor will be added as part of this permit. This permit also includes construction of walls & finish of approximately 1,000 sq. ft. in the 17,745 sq. ft. basement as storage (S1) use by this tenant. This permit involves construction of interior, non-combustible walls to create offices, conference rooms and support areas; installation of electrical, mechanical, plumbing, fire and alarm systems; wall & ceiling finishes, cabinetry, doors & hardware and floor finishes. The central stair system is being upgraded to provide a 2-hour stair enclosure and all the supporting structure of the new enclosure and the exit discharge path through the first floor lobby to the north. NOTE: THE SHELL PERMIT IS REQUIRED TO BE FINALED BEFORE OR AT THE SAME TIME AS THIS TENANT IMPROVEMENT IN ORDER FOR W&H PACIFIC TO RECEIVE LEGAL OCCUPANCY WITH ISSUANCE OF A CERTIFICATE OF OCCUPANCY. DRH05-00346 & CUP05-00149 (SHELL) drs

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/17/20078/20/20078/20/2007PPASS
DetailsForrest France
Fire alarm testing completed satisfactory, incorrect cd settings at two locations adjusted while on site, noted trouble on panel with an existing SD in the elevator mech. room to be repaired shortly per contractor, TI fire alarm permit finaled.