Permit Information
Permit NumberFIR07-00236
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 501 S 14TH ST
Project NameGRAND AVE HOMES BLD # 4
Customer Number 
ePlanReview 
Description
08/30/07 Revised Scope of Work
Dry side wall heads were added to protect the balconies per IFC 903.3.1.2 Work is noted as Rev. 5
Scope of Work
To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape or be evacuated, in a new 3,182-ft/2 two story, apartment building. An NFPA 13R fire sprinkler protection system is required. The system shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes dual service underground water supply, the system backflow prevention device (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD06-00077.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/12/20083/13/20083/13/2008APASS
DetailsForrest France
Previous c/n items are complete, two painted heads replaced while on site, fire sprinkler permit finaled.
INSP-Final Inspection3/10/20083/10/20083/11/2008PFAIL
DetailsForrest France
Missing some required finish items including FDC cap, "911" sign at the bell, breakaway lock at the PIV, restricted inspectors test, some items at the riser, also missing one system flow switch due to be replaced, project is not in condition for final at this time.
INSP-Sprinkler Rough-in11/26/200711/27/200711/27/2007APART
DetailsForrest France
Underground flush passed as per KR
INSP-Sprinkler Rough-in/Hydro11/16/200711/20/200711/20/2007PPART
DetailsForrest France
UG fire supply line hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro10/3/200710/3/200710/3/2007PPART
DetailsForrest France
AG hydrostatic testing passed.
INSP-Sprinkler Rough-in/Hydro9/21/20079/24/20079/24/2007PNR
DetailsForrest France
Hydrostatic test is not ready.
INSP-Sprinkler Rough-in/Hydro9/20/20079/21/20079/21/2007ANR
DetailsForrest France
System is not pressured for hydrostatic testing.
INSP-Sprinkler Rough-in/Hydro9/12/20079/13/20079/13/2007PPART
DetailsForrest France
OH rough-in is approved for cover, tenting at the second floor is okay, noted missing ball drip at the FDC check, need nailer plates at the second floor feed piping, AG hydro failed due to low start pressure, noted minor field modifications are okay.
INSP-Sprinkler Rough-in/Hydro9/10/20079/12/20079/13/2007AFAIL
DetailsForrest France
Hydrostatic testing failed due to pressures below 200psi at the guage.