Permit Information
Permit NumberFIR07-00244
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 3501 W ELDER ST
Project NameUNA MAS BLDG-2ND FLR
Customer Number 
ePlanReview 
Description
Scope of Work:
Drop 112 down heads into a new wall and ceiling layout on the 2nd floor. The build out covers 12,188 ft/2, of the 17,750 ft/2 area. All sprinkler work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This fire permit is attached to building permit: BLD06-00688. This is a shell and core permit only. Separate tenant improvement permits are required to finish this building for occupancy. The Underground permit is separate.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/13/20078/14/20078/14/2007APASS
DetailsTroy Cobbley
Permit is finaled.
INSP-Final Inspection8/9/20078/13/20078/13/2007PCANC
DetailsTroy Cobbley
Per the fitter the work is not done yet and the inspection will have to be rescheduled.
INSP-Final Inspection7/23/20077/25/20077/25/2007ANR
DetailsForrest France
Need shell and core project final prior to tenant permit final request.
INSP-Sprinkler Rough-in7/17/20077/17/20077/17/2007PPART
DetailsForrest France
Items on c/n verified for compliance, OH rough-in is approved for cover at the drop ceilings.
INSP-Sprinkler Rough-in/Hydro7/10/20077/11/20077/11/2007AFAIL
DetailsForrest France
Correction notice items are not completed as noted on the previous two inspections, still missing retaining straps at hangers, the added head outside the north common corridor is overspaced, copy room is not finished, noted field changes in the restrooms.
INSP-Final Inspection7/2/20077/3/20077/3/2007AFAIL
DetailsForrest France
Not all corrections noted at the previous inspection are finished, still missing retaining straps at two locations (server room 221, janitors 203), the copy room and restrooms are not completed, missing coverage outside the common corridor at the north side for shell protection-see approved plans for location.
INSP-Sprinkler Rough-in6/27/20076/29/20076/29/2007AFAIL
DetailsForrest France
Overspaced heads, one missing upright, missing retaining straps for hangers at several locations, some areas as red lined on plans are not yet completed, install is not approved for cover until corrections are made and re-inspected.