Permit Information
Permit NumberFIR07-00292
StatusFinaled
Name AMERICAN FIRE PROTECTION LLC
Site Address 981 W GROVE ST
Project NameSTATEHOUSE INN
Customer Number 
ePlanReview 
Description
The Permitted Work Scope:
Modify the existing sprinkler system by adding & relocating 98 down heads to accommodate a new wall and ceiling layout. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD06-02729. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The "Riser" and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/8/20075/9/20075/9/2007APASS
DetailsForrest France
Fire sprinkler final inspection passed, permit finaled.
INSP-Final Inspection5/2/20075/8/20075/8/2007APART
DetailsForrest France
Still missing ceiling tile at various locations.
INSP-Sprinkler Rough-in/Hydro4/30/20075/1/20075/1/2007APART
DetailsForrest France
OH rough-in is acceptable for cover at the remainder of drop ceiling areas within the tenant remodel, noted one leaking joint at the back hallway adjacent to the restroom vestibule.
INSP-Sprinkler Rough-in/Hydro4/27/20074/30/20074/30/2007PDEFR
DetailsForrest France
Inspection rescheduled.
INSP-Sprinkler Rough-in4/17/20074/18/20074/18/2007PPART
DetailsForrest France
OH install is approved for cover at areas as red lined and initialed on stamped plans including the kitchen, two restrooms, and two dining rooms, noted armovers supplying drops with static system pressures in excess of 100 psi. to have hangers and surge restraint within 1' of the head, freezer DP are not installed at this time.