Permit NumberFIR07-00305
StatusFinaled
Name ELECTRIC SERVICE & CONTRACT CO
Site Address 815 E PARK BLVD
Project NameFALCON BLDG
Customer Number 
ePlanReview 
Description
This permit is to install a new fire alarm system in an existing building. Fire alarm system requirements are a required manual fire alarm system, audible visual notification, fire sprinkler and HVAC monitoring, In-Duct smoke detectors, elevator shutdown/control and supervising station alarm reporting. Building permit Bld06-03180 is to renovate an existing 38,057 sq.ft. 3 story office building shell, core area and exterior to comply with approved plans and DRH06-00334. No tenant improvements or occupancy under this permit. Work to include, new exterior ramp, stairs, patio and retaining wall, construction of core area exit access hallway and new accessible restrooms located on each floor, installation of suspended ceiling in hallways and core area, remodel west stair enclosure to create one hour rated exit enclosure, install new windows and storefronts, remove portion of second floor to create a large opening between the 1st & 2nd floors, installation of new elevator, installation of new HVAC roof top units and ducting, installation of new fire sprinkler system and alarm system per NFPA #13 as regulated by the fire department. Miscellaneous related finishes. RMH
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/2/20081/2/20081/2/2008PPASS
DetailsForrest France
Corrections are complete, NFPA 72 record of completion provided and signed, fire alarm permit finaled.
INSP-Final Inspection12/18/200712/18/200712/18/2007PFAIL
DetailsForrest France
2nd floor damper needs adjustment to enable complete and reliable closure.
INSP-Final Inspection12/11/200712/13/200712/13/2007PFAIL
DetailsTroy Cobbley
Fire dampers on 2nd and 3rd floor do not close all the way.KR
INSP-Final Inspection10/29/200710/29/200710/29/2007PFAIL
DetailsForrest France
See inspection comments per K. Roule including HVAC duct detection and fire damper issues.
INSP-Final Inspection10/24/200710/25/200710/25/2007ANR
DetailsForrest France
Project is not in condition for final approval, also need to coordinate inspection with the sprinkler contractor, discussed project schedule.
INSP-Final Inspection10/24/200710/24/200710/25/2007PDEFR
DetailsForrest France
Inspection scheduled for 10/25.
INSP-Final Inspection10/11/200710/12/200710/12/2007PCANC
DetailsForrest France
###-#### - rick Note:please call 1/2 hr prior to inpsection Inspection cancelled from web by: Patricia Smith