INSP-Final Inspection | 6/25/2007 | 6/25/2007 | 6/25/2007 | P | PASS |
Forrest France
|
|
|
Noted issues from the previous inspection have been repaired, fire sprinkler permit finaled.
|
INSP-Sprinkler Rough-in | 5/23/2007 | 5/25/2007 | 5/25/2007 | P | FAIL |
Forrest France
|
|
|
One head in the storage room is blocked by an adjacent surface mounted light fixture, one pendent at the reception area is overspaced off the wall.
|