Permit Information
Permit NumberFIR07-00429
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 8853 W FAIRVIEW AVE
Project Name 
Customer Number 
ePlanReview 
Description
Scope of Work:
Add piping and 16 new heads In-Rack to protect Class IV stored on Hand Pick Racks in the mezzanine area. The system will be supplied from an existing System #1 feed main located beneath the Mezz.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR05-00731. Both this and the underground permits are attached to building permit: BLD05-02319.Original Scope of Work:
Add piping and 16 new heads with in a pick shelve arrangement to protect Class IV stored on Hand Pick Racks/Shelving below the mezzanine area. The system will be supplied from an existing System #1 feed main located beneath the Mezz. See Rev #4.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground supply was permitted separately under FIR05-00731. Both this and the underground permits are attached to building permit: BLD05-02319.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/11/20077/12/20077/12/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in7/11/20077/11/20077/11/2007PPASS
DetailsTroy Cobbley
Sprinkler rough-in passed. Permit will be ready for final when called in as such.
INSP-Final Inspection6/28/20076/29/20076/29/2007AFAIL
DetailsTroy Cobbley
Upright heads are blocked by structural members, wrog heads have been installed and with the additional 90s added to the brachlines the minumum 5% cushion is not achieved. Larger piping is going to have to be installed.