INSP-Final Inspection | 3/18/2008 | 3/19/2008 | 3/19/2008 | A | PASS |
Forrest France
|
|
|
Required corrections verified for completion, final fire alarm testing passed, permit finaled.
|
INSP-Final Inspection | 2/4/2008 | 2/4/2008 | 2/4/2008 | P | NR |
Forrest France
|
|
|
See correction notice items regarding elevator controls listed at today's inspection.
|
INSP-Alarm Testing | 2/1/2008 | 2/4/2008 | 2/4/2008 | A | FAIL |
Forrest France
|
|
|
Heat detectors at the elevator machine rooms must meet NFPA 72 2002 6.15.4.2 regarding location to the fire sprinkler head, need to relocate smoke detectors at the SE and SW elevator machine rooms away from air supply units, the firemans hat in the elevator car must flash intermittently upon activation of an alarm initiation device in the machine room or hoistway per state elevator requirements-see ASME 17.1 or excerpt printed on page 249 of NFPA 72 2002 fire alarm code handbook .
|
INSP-Final Inspection | 1/31/2008 | 2/1/2008 | 2/1/2008 | P | CANC |
Troy Cobbley
|
|
|
bill Note: appt at 1:00 pm Phone #: ###-#### To be rescheduled for monday since the contractor and I could not meet at a time that would work for both of us.
|
INSP-Final Inspection | 1/29/2008 | 1/31/2008 | 1/31/2008 | P | PART |
Forrest France
|
|
|
Bill please make after 1 pm Phone #: ###-#### Verified all noted correction items from the previous inspection dated 1/10 have been finished. Elevator recall, shunt trip, fire doors are all that remain to be tested prior to permit final (all three elevators).
|
INSP-Alarm Testing | 1/7/2008 | 1/10/2008 | 1/10/2008 | P | FAIL |
Forrest France
|
|
|
See site inspection comments completed per M. Timmerman.
|
INSP-Alarm Testing | 12/12/2007 | 12/18/2007 | 12/18/2007 | P | CANC |
Forrest France
|
|
|
bill Phone #: ###-####
|
INSP-Alarm Testing | 12/5/2007 | 12/10/2007 | 12/10/2007 | A | CANC |
Forrest France
|
|
|
bill Phone #: ###-####
|
INSP-Alarm Testing | 12/3/2007 | 12/3/2007 | 12/4/2007 | P | DEFR |
Forrest France
|
|
|
See inspection comments per site visit by M. Timmerman.
|
INSP-Final Inspection | 11/28/2007 | 11/30/2007 | 11/30/2007 | A | FAIL |
Forrest France
|
|
|
Noted several locations in need of av notification adjustment, some devices are missing, incorrect cd settings, blocked or obstructed, red lined areas on plans, discussed inspection scheduling.
|
FIR-Aging Inspection | 11/13/2007 | 11/13/2007 | 11/14/2007 | | DEFR |
Forrest France
|
|
|
wip
|