Permit Information
Permit NumberFIR07-00450
StatusFinaled
Name GENERAL FIRE INC
Site Address 222 S BROADWAY AVE
Project NameCourtyard Marriot Hotel
Customer Number 
ePlanReview 
Description
This fire alarm permit is to replace the existing building fire alarm system in a four story hotel. The replacement of the existing fire alarm control panel requires the new fire alarm control panel to meet all fire alarm code requirements in the 2003 IFC. A manual fire alarm system and required automatic interior corridor smoke detection and audible visual notification will be installed. Other fire alarm system requirements are fire sprinkler and HVAC system monitoring, elevator recall and shutdown, public and common area audible visual notification, assessable room audible visual requirements, kitchen hood monitoring, single station smoke alarms in each sleeping unit and fire alarm system audible visual requirements in public, common areas and sleeping units. No Building permit
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/18/20083/19/20083/19/2008APASS
DetailsForrest France
Required corrections verified for completion, final fire alarm testing passed, permit finaled.
INSP-Final Inspection2/4/20082/4/20082/4/2008PNR
DetailsForrest France
See correction notice items regarding elevator controls listed at today's inspection.
INSP-Alarm Testing2/1/20082/4/20082/4/2008AFAIL
DetailsForrest France
Heat detectors at the elevator machine rooms must meet NFPA 72 2002 6.15.4.2 regarding location to the fire sprinkler head, need to relocate smoke detectors at the SE and SW elevator machine rooms away from air supply units, the firemans hat in the elevator car must flash intermittently upon activation of an alarm initiation device in the machine room or hoistway per state elevator requirements-see ASME 17.1 or excerpt printed on page 249 of NFPA 72 2002 fire alarm code handbook .
INSP-Final Inspection1/31/20082/1/20082/1/2008PCANC
DetailsTroy Cobbley
bill Note: appt at 1:00 pm Phone #: ###-#### To be rescheduled for monday since the contractor and I could not meet at a time that would work for both of us.
INSP-Final Inspection1/29/20081/31/20081/31/2008PPART
DetailsForrest France
Bill please make after 1 pm Phone #: ###-#### Verified all noted correction items from the previous inspection dated 1/10 have been finished. Elevator recall, shunt trip, fire doors are all that remain to be tested prior to permit final (all three elevators).
INSP-Alarm Testing1/7/20081/10/20081/10/2008PFAIL
DetailsForrest France
See site inspection comments completed per M. Timmerman.
INSP-Alarm Testing12/12/200712/18/200712/18/2007PCANC
DetailsForrest France
bill Phone #: ###-####
INSP-Alarm Testing12/5/200712/10/200712/10/2007ACANC
DetailsForrest France
bill Phone #: ###-####
INSP-Alarm Testing12/3/200712/3/200712/4/2007PDEFR
DetailsForrest France
See inspection comments per site visit by M. Timmerman.
INSP-Final Inspection11/28/200711/30/200711/30/2007AFAIL
DetailsForrest France
Noted several locations in need of av notification adjustment, some devices are missing, incorrect cd settings, blocked or obstructed, red lined areas on plans, discussed inspection scheduling.
FIR-Aging Inspection11/13/200711/13/200711/14/2007 DEFR
DetailsForrest France
wip