Permit Information
Permit NumberFIR07-00511
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 855 W BROAD ST Unit: 300
Project Name9TH STREET WAREHOUSES
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over Head Only
Add and relocate heads to accommodate a new wall and ceiling layout on the third floor of this two story office bldg. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00625. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/22/200710/22/200710/22/2007PPASS
DetailsForrest France
Corrections verified for completion, inspection passed, permit finaled.
INSP-Final Inspection10/18/200710/19/200710/19/2007AFAIL
DetailsForrest France
Overspaced coverage due to missing upright heads at two locations in the SW corner of the tenant space, see plans for annotations, previously noted items are finished. Contractor is advised to complete a thorough field review of the installation prior to scheduling final inspection.
INSP-Final Inspection10/17/200710/18/200710/18/2007ACANC
DetailsTroy Cobbley
Overbooked. This will need to be rescheduled.
INSP-Final Inspection10/15/200710/16/200710/16/2007AFAIL
DetailsForrest France
See approved plans for areas defficient including overspaced heads, blocked heads, missing coverage, one pendent below max. listed distance from the deck.
INSP-Sprinkler Rough-in10/11/200710/12/200710/12/2007PPART
DetailsForrest France
OH rough-in is approved as noted on stamped plan set.
INSP-Sprinkler Rough-in10/3/200710/3/200710/3/2007PPART
DetailsForrest France
Added head at the storage closet below the stairs at the main entrance is acceptable, noted cloud ceilings obstructing coverage and one deleted hard lid ceilng.
INSP-Sprinkler Rough-in9/13/20079/13/20079/13/2007PPASS
DetailsTroy Cobbley
The mechanical chase in room 143 has been provided a sprinkler head and is ok to cover. The mechanical chase in room 150 is non-combustible and is ok to cover. These are the only two areas inspected.
INSP-Sprinkler Rough-in8/28/20078/29/20078/29/2007ACANC
DetailsTroy Cobbley
Due to the abundance of inspections today there was not adequate time to perform this one. It will need to be rescheduled.