Permit Information
Permit NumberFIR07-00565
StatusFinaled
Name ALARM STAR
Site Address 700 N COLE RD
Project NameCandlewood Suites Hotel
Customer Number 
ePlanReview 
Description
This fire alarm permit is to install a required manual and automatic fire alarm system in a new hotel with interior corridors. Guest rooms are shown to use fire alarm system detectors with sounder bases in lieu of single station smoke alarms. Corridor smoke detection is provided and audible visual notification throughout. The fire alarm system includes sprinkler monitoring, elevator control and shutdown; remote annunciation and nine hearing impaired guest rooms. Building Permit Bld06-01695 is to construct a 43,671 sq.ft. three story hotel with 77 80 extended stay suites per approved plans and CUP06-00018 & DRH06-00082. Grading & drainage issued under BLD06-02454. The architect has declared the extended stay units are restricted to less than 30 days to maintain the R-1 occupancy classification. This building to be fully fire sprinklered with a NFPA 13 system which will allow nonrated construction and increased story height. (Note: Plan review by outside consultant for IBC-nonstructural/IMC/IECC.)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/12/200710/12/200710/12/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Alarm Testing9/20/20079/21/20079/21/2007ADONE
DetailsTroy Cobbley
See Sam Rogers inspection comments for the entire project.
INSP-Alarm Testing9/18/20079/19/20079/19/2007ACANC
DetailsTroy Cobbley
rand Phone #: ###-####//cancelled per Sam Rogers pending approval of plan modifications 9/19/07 9:50am
INSP-Alarm Testing9/14/20079/17/20079/17/2007ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested on the first floor. Plans will need to be resubmitted due to ceiling mount a/v's are now wall mount. The location of dampers are not shown. The second and third floor sprinkler devices are not shown. First floor room numbers have been changed. Device addresses have been changed and addressable modules added.
INSP-Alarm Testing9/14/20079/14/20079/14/2007PFAIL
DetailsTroy Cobbley
Manual pull stations are mounted too high. The fire alarm panel has not been set up to dial out correctly. The inspection was stopped.