INSP-Final Inspection | 10/12/2007 | 10/12/2007 | 10/12/2007 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Alarm Testing | 9/20/2007 | 9/21/2007 | 9/21/2007 | A | DONE |
Troy Cobbley
|
|
|
See Sam Rogers inspection comments for the entire project.
|
INSP-Alarm Testing | 9/18/2007 | 9/19/2007 | 9/19/2007 | A | CANC |
Troy Cobbley
|
|
|
rand Phone #: ###-####//cancelled per Sam Rogers pending approval of plan modifications 9/19/07 9:50am
|
INSP-Alarm Testing | 9/14/2007 | 9/17/2007 | 9/17/2007 | A | DONE |
Troy Cobbley
|
|
|
See the city approved plans for devices tested on the first floor. Plans will need to be resubmitted due to ceiling mount a/v's are now wall mount. The location of dampers are not shown. The second and third floor sprinkler devices are not shown. First floor room numbers have been changed. Device addresses have been changed and addressable modules added.
|
INSP-Alarm Testing | 9/14/2007 | 9/14/2007 | 9/14/2007 | P | FAIL |
Troy Cobbley
|
|
|
Manual pull stations are mounted too high. The fire alarm panel has not been set up to dial out correctly. The inspection was stopped.
|