Permit NumberFIR07-00569
StatusFinaled
Name ELECTRIC SERVICE & CONTRACT CO
Site Address 113 N PHILLIPPI ST
Project NameB & R Properties Warehouse
Customer Number 
ePlanReview 
Description
This fire alarm quick permit is to install two duct detectors in HVAC units in a 1st time tenant improvement project and tie the detectors into a spare zone on an existing fire sprinkler monitoring panel. Building permit BLD07-00978 is to construct 78 lineal feet of demising wall to create a 4,160 square feet S-1 storage, tenant space within an existing shell building constructed under BLD06-00051. Additional work included in this permit is to construct an accessible restroom. This tenant space is located on the south/east side of this building, noted as area B on sheet A-1 of this plans. A separate permit is required for racking. NOTE: The fire sprinkler system is required for area increase and any modifications will require a separate permit. All construction shall be per the approved plans and attached comment list. MJP
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/1/20078/3/20078/3/2007APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/31/20078/1/20078/1/2007PFAIL
DetailsTroy Cobbley
The hvac units would not go into heat mode for some reason so no test was performed for shut down. I had the electrical contractor update the map at the facp and the zone list in the facp.
INSP-Final Inspection7/27/20077/30/20077/30/2007AFAIL
DetailsForrest France
No provision supplied to test duct detectors.