Permit NumberFIR07-00572
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1010 W WASHINGTON ST
Project NameBOISE HIGH SCHOOL
Customer Number 
ePlanReview 
Description
The Permitted Work Scope: Over Head Only
Add heads to accommodate a new wall and ceiling layout in the stairwells and on the 1st, 2nd & 3rd floors of this 3 story bldg. The work is limited to the noted scope on the plans only.
The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD07-00917. When tenant work affects fire sprinkler protection outside the permitted work area due to the installation of tenant-demising or new partition walls, the affected area sprinkler coverage outside the BLD permit will fall under the Fire Permit scope of work, to maintain the required fire protection within the fire sprinklered facility. The “Riser” and its supplies which include all appurtenances (including tamper, alarm and alarm monitoring) relating to the normal and correct function and integrity of this system will fall under the jurisdiction for code compliant verification.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/16/20078/17/20078/17/2007APASS
DetailsForrest France
Fire sprinkler work passed final inspection, permit finaled.
INSP-Final Inspection8/16/20078/17/20078/16/2007ACANC
DetailsForrest France
Please call 1/2 hour prior to inspection. Charles is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
INSP-Sprinkler Rough-in8/10/20078/14/20078/14/2007APART
DetailsForrest France
Noted corrections for the 1st and 2nd floor have been verified for compliance, remainder of the third floor rough-in is approved for cover.
INSP-Sprinkler Rough-in8/10/20078/10/20078/10/2007PFAIL
DetailsForrest France
Inspection concluded after 1st and 2nd floors due to the excessive number of defficiencies including overspaced heads, blocked heads, missing retaining straps at beam clamps, mixed temp. heads, mixed k-factors, missing hangers, heads in need of adjustment at drop ceilngs, some heads are still covered with painters tape and paper, etc.
INSP-Sprinkler Rough-in8/6/20078/7/20078/8/2007PPART
DetailsForrest France
OH rough-in at the 1st floor entry is okay for cover.
INSP-Sprinkler Rough-in8/1/20078/3/20078/3/2007APART
DetailsForrest France
Third floor classrooms as noted on approved plans are okay for cover, noted one leaking swing joint to be repaired-see plans for location.