Permit Information
Permit NumberFIR07-00579
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 6411 W FAIRFIELD AVE
Project NameMcKinley Elementary School
Customer Number 
ePlanReview 
Description
Overhead-Scope of Work:
Beginning from 5’-0” out side the bldg, install a 6” ready riser leading up and into the riser room of this new 59,007-ft/2 bldg. The over head portion of the project includes installing two wet system risers and one dry system. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD07-00143. This permit is also attached to the Underground work permit FIR07-00461.
08/13/07 Plan Review Comments
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/21/20085/21/20085/21/2008PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Sprinkler Rough-in/Hydro3/28/20083/31/20083/31/2008APASS
DetailsTroy Cobbley
The overhead hydro test passed. This included the fdc.
INSP-Sprinkler Rough-in/Hydro3/27/20083/28/20083/28/2008PCANC
DetailsTroy Cobbley
OH Hydro Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
INSP-Sprinkler Rough-in/Hydro3/26/20083/27/20083/27/2008PPASS
DetailsTroy Cobbley
OH Hydro Inspection for the gym area passed.
INSP-Sprinkler Rough-in3/11/20083/11/20083/11/2008PPART
DetailsTroy Cobbley
The upright sprinkler heads are located too far from the lower deck area, at the overbuilds, where the insulation has not been installed. All piping can be covered except at the overbuild areas. One exception is the cafeteria area where Mike, the project superintendant, will provide a photograph of an overbuild area that needs addressed.
INSP-Sprinkler Rough-in2/21/20082/22/20082/22/2008APART
DetailsTroy Cobbley
See the city approved plans for rough-in piping passed. Areas include the kitchen and cafeteria. Two small overbuilds lack upright sprinkler protection and will require heads. The entry way piping is being changed and will need Brian Johnsons approval prior to installation and inspection.
INSP-Sprinkler Rough-in2/7/20082/8/20082/8/2008APASS
DetailsTroy Cobbley
The inspection today was only for the two combustible pockets at the east entrance. Both of the pockets have been filled with insulation and can be covered.
INSP-Sprinkler Rough-in1/25/20081/28/20081/28/2008APASS
DetailsTroy Cobbley
The remaining piping to be inspected is the girls and boys restrooms and cafeteria. The sprinkler drops have not been installed yet either.
INSP-Sprinkler Rough-in1/24/20081/25/20081/25/2008APASS
DetailsTroy Cobbley
The sprinkler rough-in for the gymnasium is passed. See the plans for the areas to the south of the gym that were inspected. The piping above the mechanical mezzanine was not inspected due to time constraints.
INSP-Sprinkler Rough-in1/10/20081/11/20081/11/2008APASS
DetailsTroy Cobbley
See the city approved plans for areas inspected
FIR-Aging Inspection11/14/200711/14/200711/16/2007 NR
DetailsTroy Cobbley
work in progress