INSP-Final Inspection | 12/20/2007 | 12/20/2007 | 12/20/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 12/17/2007 | 12/17/2007 | 12/17/2007 | P | PASS |
Troy Cobbley
|
|
|
Above ground hydro test has passed.
|
INSP-Sprinkler Rough-in/Hydro | 12/6/2007 | 12/7/2007 | 12/7/2007 | A | FAIL |
Troy Cobbley
|
|
|
OH Hydro Inspection failed
|
INSP-Sprinkler Rough-in/Hydro | 12/4/2007 | 12/5/2007 | 12/5/2007 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro test failed
|
INSP-Sprinkler Rough-in/Hydro | 12/3/2007 | 12/4/2007 | 12/4/2007 | P | CANC |
Troy Cobbley
|
|
|
OH Hydro Inspection needs rescheduled due to time constraints.
|
INSP-Sprinkler Rough-in/Hydro | 11/28/2007 | 11/29/2007 | 11/29/2007 | A | FAIL |
Troy Cobbley
|
|
|
OH Hydro failed
|
INSP-Sprinkler Rough-in/Hydro | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | FAIL |
Troy Cobbley
|
|
|
Overhead hydro failed due to loss of pressure and the fdc not being tested.
|
INSP-Sprinkler Rough-in | 10/4/2007 | 10/5/2007 | 10/5/2007 | A | PASS |
Troy Cobbley
|
|
|
The sprinkler piping is ok to cover. The same patio issues as with the other building exists here as well.
|
INSP-Supply line flush | 10/3/2007 | 10/4/2007 | 10/4/2007 | A | PASS |
Troy Cobbley
|
|
|
UG Flush passed
|