Permit NumberFIR07-00605
StatusFinaled
Name ELECTRIC SERVICE & CONTRACT CO
Site Address 555 S COLE RD
Project NameIntermountain Gas Co.
Customer Number 
ePlanReview 
Description
1-14-10 PLAN MODIFICATION: This plan modification is to change candela settings on three strobes, add a relay to release door magnets on alarm, and re-land a horn/strobe circuit on the basement NAC panel to meet voltage drop requirements.


This fire alarm permit is to replace an existing simplex fire alarm control panel with a new Siemens fire alarm control panel. Work includes replacing the existing alarm devices with Siemens alarm devices for compatibility. Building requires a manual fire alarm system with full notification, HVAC and fire suppression monitoring, elevator recall and shutdown. Partial non required area detection and corridor smoke detection for fire smoke damper shutdown is shown on the 1st floor. Beam construction, partial non required area detection is also shown on the lower level. No building permit is associated with this work.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/16/20106/17/20106/17/2010APASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection11/16/200911/17/200911/17/2009AFAIL
DetailsTroy Cobbley
See the city approved plans for defiencies and locations. The plans still need to be resubmitted for a plan modification showing the door magnets and the changes to the a/v circuits.
INSP-Final Inspection9/11/20089/12/20089/12/2008AFAIL
DetailsTroy Cobbley
This inspection only covered the first floor today. See the city approved plans for locations of deficiencies which include old fire alarm devices that have not been removed, dampers that due not operate and a strobe that is mounted too low. Also the fire alarm plans need to be resubmitted showing the access controled egress doors on the east and north sides of the building that are not connected to the fire alarm system as required by IFC chapter 10
INSP-Final Inspection8/20/20088/21/20088/21/2008AFAIL
DetailsTroy Cobbley
There were no city approved drawings on site. I did however go ahead and test the audio/visuals and found one that was not operating. It was replaced and tested prior to me leaving. The spacing and candella have not been checked nor any of the initiating devices.
FIR-Aging Inspection11/7/200711/7/200711/7/2007 NR
DetailsTroy Cobbley
Per rick there are still issues with the freight elevator being used as a passenger elevator. But job is nearly ready to go.