Permit Information
Permit NumberFIR07-00624
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 345 W BOBWHITE CT Unit: 200
Project NameSPR-PCS Edventure TI
Customer Number 
ePlanReview 
Description
Debest Fire Protection to relocate 3 SSP's and add 3 SSP's to accomondate new tenant improvements. Existing sprinkler heads are standard response and new heads will be standard response.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/21/20078/21/20078/21/2007PPASS
DetailsForrest France
Fire sprinkler permit for the TI modifications passed.
INSP-Final Inspection8/16/20078/17/20078/17/2007APART
DetailsForrest France
Final pending installation of ceiling tile and escutcheons at all areas.
INSP-Sprinkler Rough-in8/16/20078/17/20078/17/2007APART
DetailsForrest France
Verified required corrections have been made, overhead installation is approved for cover at the drop ceilings.
INSP-Final Inspection8/16/20078/16/20078/16/2007PCANC
DetailsTroy Cobbley
The sprinkler fitter needs additional time to complete the work. He is going to reschedule for tomorrow. No inspection performed.
INSP-Sprinkler Rough-in8/16/20078/16/20078/16/2007PCANC
DetailsTroy Cobbley
The sprinkler fitter needs additional time to complete the work. He is going to reschedule for tomorrow. No inspection performed.
INSP-Final Inspection8/14/20078/15/20078/15/2007AFAIL
DetailsForrest France
Two heads at the waiting area exceed min. spacing allowed, need to provide verification that the existing system design will support more than one head piped off a single 1" outlet (noted 4 heads are supplied off one 1" outlet at the lobby) or install heads as shown on approved plan.