INSP-Final Inspection | 4/8/2010 | 4/8/2010 | 4/8/2010 | P | PASS |
Forrest France
|
|
|
Fire alarm permit finaled.
|
INSP-Alarm Testing | 10/17/2007 | 10/19/2007 | 10/19/2007 | A | PART |
Forrest France
|
|
|
contact person -Robert Phone #: ###-#### Internet Inspection Request from: Robert Gobler Final pending resolution of the tamper switch issue at the exisitng yard PIV between the two buildings.
|
INSP-Final Inspection | 10/16/2007 | 10/16/2007 | 10/17/2007 | P | CANC |
Troy Cobbley
|
|
|
I could not reach contractor to schedule the test. robert Phone #: ###-####
|
INSP-Alarm Testing | 10/8/2007 | 10/9/2007 | 10/9/2007 | A | PART |
Forrest France
|
|
|
Permit final pending PIV tamper switch, tamper at hose system, one flow switch in need of adjustment, and the flow switch at the hose system as noted on plans, remainder of fire alarm work tested satisfactory including all other zones, FACP, monitoring, etc., also need to sign record of completion forms.
|
INSP-Final Inspection | 3/30/2010 | 3/30/2010 | | P | |
Forrest France
|
|
|
Robert Phone #: ###-####
|
INSP-Conference | 10/19/2007 | 10/22/2007 | | A | |
Forrest France
|
|
|
PIV issue
|