INSP-Final Inspection | 11/1/2007 | 11/1/2007 | 11/1/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Sprinkler Rough-in | 10/30/2007 | 10/31/2007 | 10/31/2007 | A | FAIL |
Troy Cobbley
|
|
|
401canopies need to be installed in the restrooms where lights are blocking pendant heads. One head needs to be added at a fixture on the sales floor and two heads are located too close to one another at another fixture on the sales floor. Plans need to be resubmitted to the city of boise due to the amount of added heads caused by the fixtures. The scope of work calls for the air compressor to be changed out which has not been done yet.
|
INSP-Sprinkler Rough-in/Hydro | 9/27/2007 | 9/28/2007 | 9/28/2007 | P | PASS |
Troy Cobbley
|
|
|
24 hour air test passed
|
INSP-Sprinkler Rough-in | 9/26/2007 | 9/27/2007 | 9/27/2007 | P | PART |
Troy Cobbley
|
|
|
The 24 hour air test for the Garden Center was started at 11:00 with 55 psi on the guage.
|
INSP-Sprinkler Rough-in/Hydro | 9/24/2007 | 9/24/2007 | 9/24/2007 | P | PASS |
Troy Cobbley
|
|
|
Hydro test of the garden dry pipe system passed.
|
INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 | A | PART |
Troy Cobbley
|
|
|
The overhead piping in the garden area only is ok. The tie with the store system has not been made yet. The four way bracing at the 4" drop down is not done yet. It appears that the hydraulic node points in the calculations are not connected correctly. I contacted Brian about this.
|