INSP-Final Inspection | 2/14/2008 | 2/15/2008 | 2/15/2008 | A | PASS |
Forrest France
|
|
|
Corrections verified for compliance, final inspection passed, permit finaled.
|
INSP-Final Inspection | 2/4/2008 | 2/5/2008 | 2/5/2008 | A | FAIL |
Forrest France
|
|
|
Missing two heads at the underfloor area relocated branchline, one underfloor head adjacent to the new stocker is not supplied by 1 1/4 per plan, need to relocate one OH sprinkler outside the new tool-locate per approved drawings.
|
FIR-Aging Inspection | 1/15/2008 | 1/15/2008 | 1/15/2008 | | DEFR |
Forrest France
|
|
|
Pending permit work site inspection request.
|