Permit Information
Permit NumberFIR07-00854
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 2604 W STATE ST
Project NameST MARY'S CATHOLIC CHURCH ADD.
Customer Number 
ePlanReview 
Description
underground Scope of Work:
Beginning from an existing 8” tapping tee & 6” gate valve located in the street, run 43’-0” of 6” C-900 out and stub up into the future 9,750-ft/2 type VB, single story structure. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire “Inspection Card” are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code. This permit is attached to building permit: BLD07-01654.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/16/20086/16/20086/16/2008APASS
DetailsForrest France
UG fire supply line permit finaled.
INSP-Sprinkler Rough-in/Hydro4/3/20084/4/20084/4/2008ADONE
DetailsForrest France
Under ground hydro completed.Passed. KR
INSP-Sprinkler Rough-in/Hydro3/3/20083/3/20083/3/2008PFAIL
DetailsForrest France
Wrong permit number called in for inspection, was intended for the project related overhead permit work- Completed a preliminary walkthrough while on site of the narthex and sanctuary area-see approved plans for annotations. Noted main pipe size discrepancy at one area, CPVC piping has been used for several branchlines but no indication is made to that affect on the plans or review notes.
INSP-Supply line flush2/20/20082/21/20082/21/2008PPART
DetailsForrest France
Under ground flush complete. Hydro test has not been completed. KR
INSP-Supply line flush2/19/20082/20/20082/20/2008PCANC
DetailsForrest France
Inspection rescheduled per contractor due to coordination with United Water company.
INSP-Sprinkler Rough-in2/14/20082/15/20082/15/2008PPART
DetailsForrest France
Remainder of of uderground piping ok to cover.KR
INSP-Sprinkler Rough-in11/1/200711/2/200711/2/2007APASS
DetailsTroy Cobbley
The underground from the inside stubin to 16' out is ok to cover. See the city approved plans for piping.