Permit NumberFIR07-00883
StatusFinaled
Name QUALITY ELECTRIC INC
Site Address 190 E BANNOCK ST
Project NameST LUKES-S EAST + E ANNEX
Customer Number 
ePlanReview 
Description
This fire alarm permit is to add area smoke detection per submitted plans in the Southeast Peds rooms and Peds admin area. Add In-Duct smoke detectors as shown on the drawings provide audible visual notification with a new NAC Circuit 15 on existing FACP-02 booster #5. Building Permit BLD07-01692 is to remodel approximately 12,750 sq. ft. of existing hospital area to update and improve patient care services & for operating room prep and recovery and support services. Work includes select interior demolition; construction of non-combustible, non-rated & fire-rated, fire-resistive walls; upgrade of electrical, mechanical, plumbing, med gas, sprinkler and alarm systems; suspended ceiling grid, interior finishes and millwork, all per reviewed plans. drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/4/20082/5/20082/5/2008APASS
DetailsForrest France
Remainder of fire alarm testing passed per scope of alarm work for phase 2, also tested one av and two SD as clouded and initialed on this set of approved plans for an adjacent permit area.
INSP-Final Inspection1/7/20081/8/20081/8/2008PPART
DetailsForrest France
FA testing passed for permit area scope of work except as indicated on plans for room 169 which is not completed and a/v in restroom 167 missed for function verification during initial inspection.